Savings Comparison Analysis |
|||||||
![]() |
|||||||
UTR1-814G16CSP Data without a Cain System Combustion source: Engine Generator Heat Sink: 50% Glycol / 50% Water Loop Waste Exhaust Temp: 645 °F Water Temp Inlet:250°F SCFM: 6,739 Fuel Type: Natural gas O2 Content: N/A Excess Air: N/A Fuel Cost Per Therm: $0.60 Annual Operating Hours: 6,000 Performance with a Cain System Circulating Liquid Flow : 400 GPM Final Exhaust Temp: 357 °F Water Temp. Outlet: 263.3 °F Water Pressure Drop: 0.04 PSIG Exhaust Pressure Drop: 2.00 WC" Btu/hr Recovered: 2,341,000 Total Cost: $22,455 Payback: 4.8 months Annual Return On Investment: 250 % Annual Savings: $56,176
|
|
||||||